| DC1 | DC2 | |
|---|---|---|
| Municipal | Vendor: CenterPoint Pull: 6000 Amps over to 2 Transformers Service level: Critical Customer - similar to Hospital Service level | Vendor: CenterPoint Pull: 3000 Amps over to 1 Transformer Service level: Critical Customer - similar to Hospital Service level |
| Generators | Generator 1
Power Plant: 16 Cylinder 3000 horse power Cummins Marine Grade Diesel Gen Set:ONAN Wattage: 1250 Kw Deployment: Zone Generator 2 Power Plant: 16 Cylinder 3000 horse power Cummins Marine Grade Diesel Gen Set:ONAN Wattage: 1500 Kw Deployment: Zone Each Generator is responsible for power in a specific zone of Datacenter 1. The Power plants are tested weekly. The Generators are load tested monthly. The system is inspected quarterly. |
Generator 1
Power Plant: 16 Cylinder 3000 horse power Cummins Marine Grade Diesel Gen Set:ONAN Wattage: 2000 Kw Deployment: Load Sharing Generator 2 Power Plant: 16 Cylinder 3000 horse power Cummins Marine Grade Diesel Gen Set:ONAN Wattage: 2000 Kw Deployment: Load Sharing Both Generators handle the all the same load at DC2 with the help of paralleling gear. When a service outage occurs both generators will start for 5 minutes. If the total load is less then 33% of capacity one generator will shutdown. If the load reaches 80% of capacity the other generator will turn on. The Power plants are tested weekly. The Generators are load tested monthly. The system is inspected quarterly. |
| Power Switching | In the event of a service outage from CenterPoint, the generators will turn over and power will be switch automatically in seconds. This system is tested every month. | In the event of a service outage from CenterPoint, the generators will turn over and power will be switch automatically in seconds. This system is tested every month. |
| UPS | Currently there are 5 375 Kw Mitsubishi | Currently there are 4 375 Kw Mitsubishi |
| Cooling Units | AC Units: Data Aire 30 Ton
Number of Units: 30 Total tonnage: 900 Tons Total amps pulled for cooling: 1130 amps |
AC Units: Leibert 30 Ton
Number of Units: 17 Total tonnage: 510 Tons Total amps pulled for cooling: 640 amps |